R&S®NGMD, NGL, NGT Multiple output benchtop Power Supplies

Compact, low noise, general purpose

Specifications

Type Setting ranges Resolution Max. deviation of output for Zout for tr for Max. PARD Over- voltage protec. Dimens. W × H × D in mm (Weight in kg)
ΔV AC supply ±10% Δtamb –10 °C to +40°C
R&S®... Voltage in V Current in A V in % I in % V (in %) I (in %) V (%/°C) I (in %) V in mΩ I in kΩ V
φs
Vrms in mV Irmsin mA
Dual Power Supplies
NGMD35 0.01 to 35
(2x)
0.01 to 1 0.02 0.02 0.001 0.001 0.01 0.01 3.5 175 50 0.4 0.02 190/172/
278 (8)
Triple Power Supplies
NGL35 0.01 to 35
(3x)
0.01 to 0.6 contin. 1 0.01 0.2 0.1 0.1 3.5 15 75 0.2 190/172/
278 (7)
NGT20 0.01 to 20 (2x)
0.01 to 6 (1x)
0.01 to 1
0.01 to 5
0.02 1 0.01 0.2 0.01 0.1 2
1
9
0.4
75
75
0.15
0.2

190/172/
278 (7)
NGT25 0.01 to 25 (2x)
0.01 to 6 (1x)
0.01 to 0.8
0.01 to 5
0.02 1 0.01 0.2 0.01 0.1 2.5
1
10
0.4
75
75
0.2
0.2


190/172/
278 (7)
NGT35 0.01 to 35 (2x)
0.01 to 6 (1x)
0.01 to 0.6
0.01 to 5
0.02 1 0.01 0.2 0.01 0.1 3.3
1
15
0.4
75
75
0.25
0.2


190/172/